Issue:


On 31st October 2023, one of our ATSPACE engineers visited a site in Prescot, Merseyside, to conduct a ventilation test on two plots that had extract fans installed in the bathrooms and kitchens. The test involved measuring the airflow rates of the fans using a calibrated anemometer and comparing them with the design specifications. However, the testing results showed that both plots failed to meet the required flow rates for the fans, which were 15 litres per second (l/s) for the bathroom fans and 30 l/s for the kitchen fans. The actual flow rates measured were only 10 l/s and 20 l/s respectively.

Solution:


The ATSPACE engineer suspected that there was a problem with the ducting behind the fans, which could affect the performance of the ventilation system. He used his extensive knowledge of what can affect the flow rates of a ventilation fan and inspected the ducting carefully.

He found that there were several issues with the ducting, such as:


• The ducting was too long and had too many bends, which increased the resistance and reduced the airflow.
• The ducting was not properly sealed at the joints, which caused air leakage and pressure loss.
• The ducting was not insulated, which could lead to condensation and mould growth.
The ATSPACE engineer explained the situation to Keith, who was the client onsite, and suggested some possible solutions to rectify the issues. They agreed to work together to fix the ducting by:
• Shortening and straightening the ducting as much as possible, while ensuring that it met the minimum length requirement of 300 mm from the fan outlet.
• Sealing all the joints with mastic or tape to prevent air leakage.
• Insulating the ducting with suitable material to prevent condensation and heat loss.

Result:


After fixing the ducting, the ATSPACE engineer retested both plots and found that they both fully complied with Part F of the building regulations. The flow rates of the fans increased to 16 l/s for the bathroom fans and 32 l/s for the kitchen fans, which exceeded the design specifications. The client was very satisfied with the outcome and thanked the ATSPACE engineer for his professionalism and expertise. The ATSPACE engineer completed his report and submitted it to the client along with his certificate of compliance.

Previous Article: 18 x New Build Apartments & 6 Houses Next Article: Armthorpe

"ATSPACE has provided , and continues to provide, an outstanding service to a high standard."

Andy Gilliver, Persimmon Homes

Results

 

 

"A very prompt and efficient service that dealt with every aspect of my requirements in a professional way. If you're in need of any testing requirements to meet building regulations I'd recommend ATSPACE every time."

Mynott Associates Limited

Results

"We have Found ATSPACE Services reliable, professional and friendly at a competitive Price."

Lyndsay Thrower, Taylor Wimpey

Results

"Thank you for the Smoke shaft Air Pressure Test. The whole experience with ATSPACE has been a pleasure from the start and we are looking forward to working with you on the next job.”

Brian Keane, C.E.O, Cameron Ventures Group

Results

"Just a note to thank ATSPACE for the excellent service received on this most recent project. Your engineer put himself out to ensure that the Smoke shaft Air Pressure Test was carried out with the minimum of fuss (in a very tricky environment) and was a pleasure to have on site."

Olly Wigg Director, Bowson Leeway Homes

Results

Testimonials

Trusted by 9K+ businesses
hill
taylor wimpey
logo-mace
Willmott_Dixon_logo
Copyright © 2022 Atspace Ltd. Website Design by Insynth Marketing Ltd.